Item | ZFP500 | ZFP1000 | ZFP2000 | ZFP3000 | |||
Dry powder filling amount(Kg) | ≤510 | ≤952 | ≤1496 | ≤2380 | |||
Fire class | D | ||||||
Supercharging time(s) | ≤20 | ||||||
Spraying time(s) | ≥60 | ||||||
Residual powder ratio | ≤10% | ||||||
Operating temperature range(ºC) | -20~+50 | ||||||
System boot mode | Automatic, manual, mechanical emergency | ||||||
Dry powder tank | Volume(m3) | 0.75 | 1.4 | 2.2 | 3.5 | ||
Design pressure(MPa) | 1.6 | 1.8 | 1.6 | ||||
Working pressure(MPa) | 1.5 | 1.6 | 1.55 | ||||
Expellant gas cylinder | Gas type | N2 | |||||
Volume(L) | 70 | ||||||
Number of cylinders | 2 | 4 | 9 | 13 | |||
Filling pressure (+20ºC)MPa |
13.5 | ||||||
Starting cylinder |
Gas type | N2 | |||||
Volume(L) | 8 | ||||||
Filling pressure (+20ºC)MPa |
6.0 |